    1616Die Zellen sind je Batterie durchnummeriert, vom Minus-Pol beginnend.
    1717
    18 ||= Batterie-Name =||= BMS BT MAC =||= Balancer BT MAC =||= Inbetriebnahme =||
    19 ||BatterieSpeicherBeeskow || 60:6E:41:18:16:D8 || 3C:A5:51:95:81:53 || 2023-09-09||
    20 ||BatterieSpeicherFriedland || 60:6E:41:18:11:52 || 3C:A5:51:95:7D:E1 || 2023-11-30||
    21 ||BatterieSpeicherKossenblatt || 60:6E:41:18:14:B3 || 3C:A5:51:95:7E:32 || 2023-12-15||
    22 ||BatterieSpeicherLindenberg || 60:6E:41:18:17:E3 || 2B:80:03:F5:9D:42 || 2023-12-23||
    23 ||BatterieSpeicherGrossRietz || XX:XX:XX:XX:XX:XX || XX:XX:XX:XX:XX:XX || 2026-MM-TT||
     18||= Batterie-Name =||= BMS BT MAC =||= Balancer BT MAC =||= Inbetriebnahme =||= BMS BLE-Pin =||= BMS PWD =||
     19||BatterieSpeicherBeeskow || 60:6E:41:18:16:D8 || 3C:A5:51:95:81:53 || 2023-09-09||  ||  123456||
     20||BatterieSpeicherFriedland || 60:6E:41:18:11:52 || 3C:A5:51:95:7D:E1 || 2023-11-30||  ||  123456||
     21||BatterieSpeicherKossenblatt || 60:6E:41:18:14:B3 || 3C:A5:51:95:7E:32 || 2023-12-15||  ||  123456||
     22||BatterieSpeicherLindenberg || 60:6E:41:18:17:E3 || 2B:80:03:F5:9D:42 || 2023-12-23||  ||  123456||
     23||BatterieSpeicherGrossRietz || A4:C1:38:06:1A:AC || 38:36:12:01:8C:5B || 2026-10-20||  ?1234 / 0000?  ||  123654  ||
    2424
    2525Hier geht es zu den BatterieSpeicherZellen, Lieferlosen, Seriennummern etc.
    … …  
    2828== Seplos V2 10E BMS und Neey Balancer Einstellungen
    2929
     30Dieser Abschnitt muss neu organisiert werden:
     31
     32* nicht mehr alle Batterien haben ein Seplos-BMS haben,
     33* es gibt auch Batterien mit JK-BMS
     34* es gibt unterschiedliche Balancer (alle Marke Neey, unterschiedliche Stromstärke). Die JK-BMS können selber balancieren,
     35* die Batterien haben unterschiedliche Kapazitäten
     36* es gibt Batterien, die nicht im Verbund laufen, z.B. weil sie eine andere Systemspannung haben (12 V, 24 V)
     37
    3038Hier geht es zum [[SeplosV2-10E-Verhalten|Seplos V2 10E Verhalten]].
    3139
    3240Der Neey hat einen [[NeeyFactoryCalibrationMode|Factory Calibration Mode]].
    3341
    34 || Parameter-Name ||  Wert  ||  !Seplos/Neey  || projizierter Wert für die Batterie \\ (pro Zelle, gesamte Batterie) ||
    35 || # of Cells ||  16  ||  S+N  ||  ||
    36 || Battery Capacity ||  280 Ah||  S+N  ||  ~14.3 kWh||
    37 || Balancer-Start-Voltage ||  3.45 V||  S+N  ||  55.20 V||
    38 || Balancer-Stop-Voltage ||  3.40 V||  N  ||  54.40 V||
    39 || Balancer-Diff.-Voltage ||  0.005 V||  S+N  ||  ||
    40 || Single high voltage alarm ||  3.55 V||  S  ||  56.80 V||
    41 || Single high voltage recovery ||  3.50 V||  S  ||  56.00 V||
    42 || Single low voltage alarm ||  2.75 V||  S  ||  44.00 V||
    43 || Single low voltage recovery ||  2.90 V||  S  ||  46.40 V||
    44 || Cell overvoltage protection ||  3.65 V||  S  ||  58.40 V||
    45 || Cell overvoltage protection return ||  3.55 V||  S  ||  56.80 V||
    46 || Cell undervoltage protection ||  2.50 V||  S  ||  40.00 V||
    47 || Cell undervoltage protection return ||  2.75 V||  S  ||  44.00 V||
    48 || Total voltage overvoltage protection ||  57.60 V||  S  ||  3.60 V||
    49 || Total voltage overvoltage recovery ||  57.00 V||  S  ||  3.5625 V||
    50 || Total voltage high voltage alarm ||  57.00 V||  S  ||  3.5625 V||
    51 || Total voltage high voltage recovery ||  56.80 V||  S  ||  3.55 V||
    52 || Total voltage low voltage alarm ||  46.40 V||  S  ||  2.90 V||
    53 || Total voltage low voltage recovery ||  48.00 V||  S  ||  3.00 V||
    54 || Total voltage undervoltage voltage protection ||  44.00 V||  S  ||  2.75 V||
    55 || Total voltage undervoltage voltage recovery ||  46.40 V||  S  ||  2.90 V||
     42|| Parameter-Name ||  BMS  ||  Neey  || projizierter Wert für die Batterie \\ (pro Zelle, gesamte Batterie) ||
     43|| # of Cells ||  16  ||  16  ||  ||
     44|| Battery Capacity ||  280 Ah||  280 Ah||  ~14.3 kWh||
     45|| Balancer-Start-Voltage ||  3.60 V||  3.43 V||  55.20 V||
     46|| Balancer-Stop-Voltage ||  3.40 V||  3.40 V||  54.40 V||
     47|| Balancer-Diff.-Voltage ||  0.005 V||  0.002 V||  ||
     48|| Single high voltage alarm ||  3.55 V||     ||  56.80 V||
     49|| Single high voltage recovery ||  3.50 V||     ||  56.00 V||
     50|| Single low voltage alarm ||  2.75 V||     ||  44.00 V||
     51|| Single low voltage recovery ||  2.90 V||     ||  46.40 V||
     52|| Cell overvoltage protection ||  3.65 V||     ||  58.40 V||
     53|| Cell overvoltage protection return ||  3.55 V||     ||  56.80 V||
     54|| Cell undervoltage protection ||  2.50 V||     ||  40.00 V||
     55|| Cell undervoltage protection return ||  2.75 V||     ||  44.00 V||
     56|| Total voltage overvoltage protection ||  57.60 V||     ||  3.60 V||
     57|| Total voltage overvoltage recovery ||  57.00 V||     ||  3.5625 V||
     58|| Total voltage high voltage alarm ||  57.00 V||     ||  3.5625 V||
     59|| Total voltage high voltage recovery ||  56.80 V||     ||  3.55 V||
     60|| Total voltage low voltage alarm ||  46.40 V||     ||  2.90 V||
     61|| Total voltage low voltage recovery ||  48.00 V||     ||  3.00 V||
     62|| Total voltage undervoltage voltage protection ||  44.00 V||     ||  2.75 V||
     63|| Total voltage undervoltage voltage recovery ||  46.40 V||     ||  2.90 V||
    5664