| | 16 | |
| | 17 | |
| | 18 | == Seplos V2 10E und Neeey-Balancer Einstellungen |
| | 19 | |
| | 20 | Hier geht es zum [[SeplosV2-10E-Verhalten|Seplos V2 10E Verhalten]]. |
| | 21 | |
| | 22 | || Parameter-Name || Wert || |
| | 23 | || Balancer-Start-Voltage || 3.45 V|| |
| | 24 | || Single high voltage alarm || 3.50 V|| |
| | 25 | || Single high voltage recovery || 3.48 V|| |
| | 26 | || Cell overvoltage protection || 3.66 V|| |
| | 27 | || Cell overvoltage protection return || 3.60 V|| |
| | 28 | || Total voltage overvoltage protection || 57.80 V|| |
| | 29 | || Total voltage overvoltage recovery || 57.50 V|| |
| | 30 | || Total voltage high voltage alarm || 57.00 V|| |
| | 31 | || Total voltage high voltage recovery || 57.50 V|| |
| | 32 | || Cell undervoltage protection || 2.50 V|| |
| | 33 | || Cell undervoltage protection return || 2.70 V|| |
| | 34 | |
| | 35 | ---- |
| | 36 | |
| | 37 | || Schalter-Name || Zustand || |
| | 38 | || Single Cell High Voltage Alarm || off || |
| | 39 | || Total voltage High Voltage Alarm || ON || |
| | 40 | |
| | 41 | == Deye Sun-12k-SG04LP3 Parameter |
| | 42 | |
| | 43 | || Parameter-Name || Wert || |
| | 44 | || //charge voltage limit// unabhängig von \\ "Total voltage overvoltage protection" || 57.00 V|| |
| | 45 | || //absorption voltage// || 56.20 V|| |
| | 46 | || //absorption time// || >30 min|| |
| | 47 | || //xxx// || xx V|| |