| 43 | | || Parameter-Name || Wert || |
| 44 | | || //charge voltage limit// unabhängig von \\ "Total voltage overvoltage protection" || 57.00 V|| |
| 45 | | || //absorption voltage// || 56.20 V|| |
| 46 | | || //absorption time// || >30 min|| |
| 47 | | || //xxx// || xx V|| |
| | 43 | || Parameter (-Name) || Wert\\(Batterie) || Wert\\(pro Zelle für 16s) || |
| | 44 | || //charge voltage limit// unabhängig von \\ "Total voltage overvoltage protection" || 57.00 V|| 3.5625 V|| |
| | 45 | || //absorption voltage// \\ CV-Charge-Phase || 56.80 V|| 3.55 V|| |
| | 46 | || //absorption voltage// \\ optional niedriger für längere Sättigungsphase\\(Absorption, CV-Charge) || 55.20 V|| 3.45 V|| |
| | 47 | || //absorption time// \\(>30 min, Seplos-BMS nutzt diese Zeit für den 100%-Reset)\\(der Balancer arbeitet in dieser Zeit) || 60 min|| 60 min|| |
| | 48 | || //float voltage// || 54.00 V|| 3.375 V|| |
| | 49 | || //float voltage// \\ optional niedriger... || 53.60 V|| 3.35 V|| |
| | 50 | || //equalization// || off / float voltage|| never for LFP|| |
| | 51 | || //low temperature cut-off// || 5 °C|| 5 °C|| |
| | 52 | || //xxx// || xx V|| xx V|| |